SPECIFICATIONS

Heat Sensor:

Combination fixed temperature and rate of rise, alarms at

57°C (135°F) ambient or temp. increases greater than
9°C (15°F) per min.

Detector Spacing:

70ft (21.3m) center to center

Environmental Limits:

Temperature: 32° to 100°F (0° to 38°C)
Humidity: 0 to 93% rh, non-condensing

Voltage:

15.2 to 19.95 Vdc (19 Vdc nominal)

Operating Current:

Stand-by: 45

µ

A at 19V

Alarm: 45

µ

A at 19V

Emergency stand-alone alarm mode: 18mA
Pulse current: 100

µ

A (100 msec)

During communication: 9 mA max.

Construction:

High impact engineering polymer

Finish:

White

Compatible Mounting Bases:

SIGA-SB standard base
ADT-RB relay base
ADT-IB and ADT-IBS isolator base

LED Operation:

On-board green LED: Flashes when polled
On-board red LED: Flashes when in alarm
Both LEDs: On steady when in alarm (stand-alone)

Compatible remote red LED:

Flashes when in alarm

Compatibility:

Signature loop controller

Address Requirements:

1 device address

Accessories:

SIGA-SB: Detector mounting base
ADT-RB:

Detector mounting base with relay

ADT-IB:

Detector mounting base with fault isolator

ADT-IBS:

Same as above, with loop continuity switch

SIGA-LED: Remote alarm LED
SIGA-TS:

Trim skirt (supplied with 4in bases)

74-3346 J.S. 12-99