4-2. TROUBLESHOOTING
(Continued)
Problem
Cause
Correction
Slow to decrease
Condenser obstructed by dirt.
Clean the Condenser.
in temperature (decline in
performance)
Evaporator iced up.
Perform a de-icing cycle.
Refrigerating problem
Check refrigeration circuit and
components.
Display temperature does
In Frigiprobe mode, the display
Normal
not match the actual inlet air
shows the product temperature.
temperature. (No alarm)
In timer mode, or hold mode,
Ohm out the probe and check
the probe may be showing the
the reading with the table on
wrong temperature.
page 4-5. Change the probe if
it is out of tolerance.
Green compressor indicator
Compressor and condenser fan
light on and the compressor
do not work:
not working, or working
- Faulty contactor
Check contactor and change if
sometimes.
neccessary.
- Faulty control board relay-no
Replace control board.
voltage across terminals 10-11.
Compressor works, but condenser
fan does not:
- Faulty condenser fan
Replace fan.
Compressor and condenser fan
work together:
- Faulty protection component
Check items and replace if
for the compressor (overload
neccessary.
protector, potential relay, start
and run capacitor)
- Faulty overload protector of
Check fan and replace if
condenser fan.
necessary.