N-ANN-RLY Relay Module
Communication Pair Wiring Distance: FACP to last ANN-BUS Module
Total Worst Case
Current Draw (amps)
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
1,852 ft. (565 m)
4,688 ft. (1,429 m)
* 6,000 ft. (1,829 m) * 6,000 ft. (1,829 m)
0.200
926 ft. (282 m)
2,344 ft. (715 m)
3,731 ft. (1,137 m)
5,906 ft. (1,800 m)
0.300
617 ft. (188 m)
1,563 ft. (476 m)
2,488 ft. (758 m)
3,937 ft. (1,200 m)
0.400
463 ft. (141 m)
1,172 ft. (357m)
1,866 ft. (569 m)
2,953 ft. (900 m)
0.500
370 ft. (113 m)
938 ft. (286 m)
1,493 ft. (455 m)
2,362 ft. (720 m)
0.600
309 ft. (94 m)
781 ft. (238 m)
1,244 ft. (379 m)
1,969 ft. (600 m)
0.700
265 ft. (81 m)
670 ft. (204 m)
1,066 ft. (325 m)
1,687 ft. (514 m)
0.800
231 ft. (70 m)
586 ft. (179 m)
933 ft. (284 m)
1,476 ft. (450 m)
0.900
206 ft. (63 m)
521 ft. (159 m)
829 ft. (253 m)
1,312 ft. (400 m)
1.000 (max.)
185 ft. (56 m)
469 ft. (143 m)
746 ft. (227 m)
1,181 ft. (360 m)
Connect to FACP ANN-BUS
and /or next device
Connect to FACP or UL listed Power Supply for
Fire Protective Signaling and/or next device