Technical Description

TrueDRY DR65 uses a refrigeration system similar to
an air conditioner to remove heat and moisture from
incoming air and add heat to the air that is discharged.
Hot, high-pressure refrigerant gas is routed from the
compressor to the condenser coil. The refrigerant is
cooled and condensed by giving up its heat to the
air that is about to be discharged from the unit. The
refrigerant liquid then passes through a filter drier and
capillary tubing which causes the refrigerant pressure
and temperature to drop. It next enters the evaporator
coil where it absorbs heat from the incoming air and
evaporates. The evaporator operates in a flooded
condition, which means that all the evaporator tubes
contain liquid refrigerant during normal operation. A
flooded evaporator should maintain nearly constant
pressure and temperature across the entire coil, from
inlet to outlet.

Problem

Recommended troubleshooting steps

No dehumidification. Neither

fan nor compressor run and the

ventilation timer is OFF.

1. Unit unplugged or no power to outlet.
2. Humidity control set too high or defective.
3. Loose connection in internal or control wiring.
4. Defective Compressor relay.
5. Defective control transformer.
6. Optional Condensate Pump Safety Switch open.

No dehumidification. Compressor

does not run but fan runs when

there is a call for dehumidification

and the ventilation control is OFF.

1. Defective compressor run capacitor.
2. Bad connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor.
5. Defrost thermostat open.
6. Optional Condensate Pump Safety Switch open.

Fan runs when there is a call

for dehumidification and the

ventilation control is OFF, but the

compressor cycles on and off too

frequently.

1. Low ambient temperature and/or humidity causing unit to cycle

through defrost mode.

2. Defective compressor overload.
3. Defective compressor.
4. Defrost thermostat defective.
5. Dirty air filter(s) or airflow restricted.
6. Low refrigerant charge, causing defrost control to cycle.
7. Bad connection in compressor circuit. Fan does not run with

fan switch in either position.

CONDENSER

EVAPORATOR

CAPILLARY

TUBES

ACCUMULATOR

COMPRESSOR

STRAINER/FILTER

DRIER

M27404

Troubleshooting

TrueDry DR65 Dehumidification System 69-2089EFS—11

13

CAUTION: Servicing the TrueDRY DR65 with its high pressure refrigerant system and high
voltage circuitry presents a health hazard which could result in death, serious bodily injury,
and/or property damage. Service should only be performed by a qualified service technician.