beautypg.com

Chimney & venting – Harman Stove Company 3-90-70738 User Manual

Page 6

background image

6

ChImNEY & vENTINg

Types Of Chimneys

The chimney is one of the most important, yet most

neglected and misunderstood portions of any solid

fuel burning stove installation. Do not connect this

stove to a chimney flue serving another heating de-

vice.

THE STOVE MUST BE CONNECTED TO ITS OWN

TILE-LINED FLUE. A MINIMUM FLUE SIZE OF 8” X

8” IS NECESSARY FOR PROPER OPERATION.

UNDER NO CIRCUMSTANCES SHOULD A MANUAL

FLUE DAMPER BE INSTALLED IN THE SMOKE

PIPE BETWEEN THE STOVE AND THE CHIMNEY.

NO DAMPER, HEAT SAVER OR AUTOMATIC VENT

DAMPER DEVICE SHOULD BE INSTALLED IN OR

ON THE SMOKE PIPE.

CAUTION: THE CHIMNEY MUST BE A CLASS “A”

CHIMNEY, IN GOOD OPERATING AND CLEAN

CONDITION.

NOTE: THE USE OF ALUMINUM TYPE “B” GAS

VENT FOR SOLID FUELS IS UNSAFE AND PRO-

HIBITED BY THE NATIONAL FIRE PROTECTION

AGENCY CODE.

There are three types of class “A” chimneys:

1. Masonry with tile liner, to include brick or stone. It

must be supported on grade level foundation.

2. Insulated, manufactured chimney, listed or certified

by a national test agency.

3. Triple-wall metal class “A” chimney, listed or certi-

fied by a national test agency.

If your masonry chimney has not been used for some

time, have it inspected by a qualified person. If a listed

or certified manufactured chimney is to be used, make

certain it is installed in accordance with the manufac-

turer’s instructions and all local and state codes.

The minimum recommended height for solid fuel

chimneys is 6 feet from the stove collar. The chimney

must be two feet higher than anything within ten feet.

It also must extend three feet above the point where it

intersects or exits the roof line.

In order to have a properly operating solid fuel heat-

ing system, the chimney must be capable of provid-

ing the necessary draft. The minimum required draft

is .06 inches of water column (W.C.). This must be

measured using a draft gauge. If the chimney cannot

supply this constant draft, the stove will not operate

properly. A barometric damper may be used and prop-

erly adjusted to compensate for excessive draft only.

IMPORTANT: When you measure the the draft, the

stove must be operating with sufficient time given for

the stove and chimney to warm. Burn for at least thirty

minutes. The draft reading is best taken 18” up from

the center of the flue outlet, in the connector pipe. Drill

a hole in the pipe for the meter tube, and fill it with a

screw or silicone when done with the test.

IMPORTANT: The connector pipe must be 4 gauge

or thicker.

When connecting the flue pipe to the stove, the first

section should be installed inside the stove collar. It

should be secured to the collar with, at least, three

screws or rivets.

Do not pass the connector pipe through a wall or

ceiling without first checking with your local codes. If

allowed, use only approved pass-thru methods.

NOTE: All horizontal runs of venting should have a /4

inch of rise per foot of length.

Use no more than two 90° elbows in the connector.

If a barometric damper is needed, to compensate for

excessive draft, install it only in a vertical section of

vent pipe.

The three foot, two foot, ten foot rule