Chart – Heat & Glo Fireplace 8000TRD User Manual
Page 14

14
HORIZONTAL VENTING
Kit No.
H Max. Run
DVK-01D
DVK-01TRD
24" (610 mm)
Figure 10. Corner Installation
NOTE: 8000TRD model is tested and approved
to use 45° elbows in corner installations.
However, 90° elbows will result in better per-
formance.
45-DEGREE
ELBOW
90-DEGREE
ELBOWS
H
3. Match the amount of vertical you have in the sys-
tem with the chart to find the appropriate position
to set the Flue Restrictor.
1 2 3 4 5
SETTINGS
1 2 3 4 5
Figure 9
- CHART -
Vertical
Top Vent
NG
Top Vent
LP
Rear Vent
NG
Rear Vent
LP
4'
1-1
No
Restrictor
No
Restrictor
No
Restrictor
8'
2-2
1-2
1-1
No
Restrictor
15'
3-3
3-2
2-2
1-2
20'
3-4
3-3
3-3
2-3
25'
3-4
3-3
3-3
2-3
30'
4-4
3-4
3-4
3-3
35'
4-4
3-4
3-4
3-3
40'
5-4
4-4
4-4
3-4
4. Center the Flue Restrictor on vent and secure in
place by using two self-tapping screws (see Fig-
ure 9).
5. Reinstall the Exhaust Shield.