Two elbows, Three elbows, Top vent - vertical termination - (continued) – Hearth and Home Technologies 6000GCF-IPI User Manual
Page 27
![background image](/manuals/96175/27/background.png)
Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP • 2110-900 Rev. H • 11/08
27
Figure 7.11
Two Elbows
H
1
V
1
V
2
Three Elbows
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
V
2
Top Vent - Vertical Termination - (continued)
Figure 7.12
V
1
H
1
Maximum
V
2
V
1
+ V
2
Minimum
6 in.
152 mm
3 ft
914 mm
*
*
*
1 ft
305 mm
3 ft
914 mm
*
*
*
2 ft
607 mm
6 ft
1.8 m
*
*
*
4 ft
1.2 m
12 ft
3.7 m
*
*
*
V1 + V2 + H1 = 50 ft (15.2 m) Max.
*No specifi c restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 50 ft (15.2 m)
V
1
= 6 inches (152 mm) Min.
V
1
H
1
+ H
2
V
2
V
1
+ V
2
Minimum
H
1
+ H
2
Maximum
6 in.
152 mm
3 ft
914 mm
*
*
*
3 ft
914 mm
1 ft
305 mm
3 ft
914 mm
*
*
*
3 ft
914 mm
2 ft
610 mm
6 ft
1.8 m
*
*
*
6 ft
1.8 m
4 ft
1.2 m
12 ft
3.7 m
*
*
*
12 ft
3.7 m
H
1
+ H
2
= 17 ft (5.2 m) Maximum
V
1
+ V
2
+ H
1
+ H
2
= 50 ft (15.2 m) Maximum
V
1
= 6 inches (152 mm) Minimum