OM-494 Page 50

9-3.

Run-In Procedure Using Resistance Grid

S-0684

Y

Stop engine.

Y

Do not touch hot exhaust
pipe, engine parts, or load
bank/grid.

Y

Keep exhaust and pipe away
from flammables.

1

Resistance Grid

Use grid sized for generator rated
output.

Turn Off grid.

2

Welding Generator

Place Welder Selector switch in
Welder B position (600 Amps), A/V
control in minimum position, and
both Process Selector switches in
Stick/TIG position.

3

Weld Cables

Connect grid to generator Welder B
(right) weld output terminals using
proper size weld cables with cor-
rect connectors (polarity is not im-
portant).

4

Voltmeter

5

Clamp-On Ammeter

Connect voltmeter and ammeter as
shown, if not provided on generator.

Start engine and run for several
minutes.

Set grid switches and then adjust
generator A/V control so load
equals 350 Amps at 40 volts.

Check generator and meters after
first five minutes then every fifteen
minutes to be sure generator is
loaded properly.

.

Check oil level frequently dur-
ing run-in; add oil if needed.

After one hour (minimum), place
A/V control in minimum position,
then shut down grid to remove load.
Run engine several minutes at no
load.

Y

Stop engine and let cool.

6

Engine Exhaust Pipe

Repeat procedure if wetstacking is
present.

1

3

2

5

6

+

4