Honeywell GES User Manual
Page 3
DN-6872 • 12/19/02 — Page 3 of 3
GE Series Wiring with AVS44 Sync Module
GEC Models
Conventional
Wiring
GEH/GES Models
Conventional
Wiring
6872wirc2.wmf
6872wirc1.wmf
6872wirs.wmf
Horn Ratings over Input Voltage Range of 16 – 33 V
Horn Mode
dBA @ 10' (3.048 m)
per UL 464
HIGH dB
dBA @ 10' (3.048 m)
per UL 464
LOW dB
DC (mA)
FWR (mA)
16 V
24 V
33 V
16 V
24 V
33 V
16 V
24 V
33 V
16 V
24 V
33 V
Temporal 3 2400 Hz
78
83
84
71*
75
77
13
19
24
27
37
43
Temporal 3 Mechanical
76
81
82
70*
73*
76
11
16
22
23
33
40
Temporal 3 Chime
70*
71*
71*
66*
68*
70*
9
12
15
19
24
29
Continuous 2400 Hz
81
86
87
74*
78
80
14
21
28
21
42
48
Continuous Mechanical
80
84
85
72*
76
78
13
18
25
27
37
44
Continuous Chime
70*
71*
73*
66*
68*
70*
10
12
15
19
24
30
Whoop
82
83
83
69*
72*
75
43
51
56
51
58
62
6872horn.tbl
TABLE NOTES: 1) *Operating the horn in this mode at this voltage will not meet the minimum UL reverberant sound level
required for public mode fire protective service. These settings are acceptable only for private mode fire alarm use. Use the high
dBA setting for public mode application (not applicable when using the chime tone — the chime tone is always private mode).
2) The sound output for the temporal 3 tone is rated lower, as the time the horn is off is averaged into the sound output rating.
While the horn is producing a tone in the temporal 3 mode, its sound pressure is the same as when in continuous mode.