E. Combustible Mantel

• See Figure 11.4.
• A combustible mantel may be positioned no lower than 12

in. (305 mm) above the top of the fi replace opening.

• A combustible mantel may have a maximum depth of

12 in. (305 mm).

• Combustible trim and materials cannot be placed within

6 in. (152 mm) of the fi replace opening (top or sides).

• Combustible materials projecting more than 1-1/2 in.

(38 mm) shall not be placed within 12 in. (305 mm) from
the top of the fi replace opening.

• Combustible trim must not cover the metal surfaces of

the fi replace.

• Mantel clearance is in accordance with Section 7-3.3.3

of ANSI/NFPA211.

7 ft (2134 mm)

minimum

base of fireplace

to ceiling

Combustible Wall

2 x 4
stud wall

Standoffs

Measured from top of fireplace opening

12 in./305 mm MAXIMUM

12 in./305 mm MINIMUM

Combustible
Decorative Facing

Noncombustible
Decorative Facing

Seal joint with
non-combustible
sealant

Figure 11.4 Clearances to Mantels or other Combustibles above Fireplace

Heat & Glo • HST-42D • 27177 • Rev AB • 11/08