Hearth and Home Technologies Wood Burning Fireplace HST-42D User Manual

Page 20

background image

20

40 in.

[1016 mm]

36 in.

[914 mm]

12 in.

[305 mm]

9 3/4 in.

[248 mm]

12 in.

[305 mm]

12 in.

[305 mm]

Grid represents 1 in. (25 mm) squares

FLUSH
FRONT

4 in.

[102 mm]

BRICK

FRONT

50° angle

39° angle

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

• Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.
• Framing across the top of fi replace must be above top standoffs.

You must maintain

2 in. (51 mm) min. air space

clearance from the

chimney to the

enclosure.

23 in.

(584 mm)

Note: Fireplace

Header cannot be

positioned until after

the fireplace assembly

is in place.

41 in.

(1041 mm)

Figure 6.4 Framing the Fireplace

C. Sidewalls/Surrounds

• Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fi replace opening.
• Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed within the gridded area,

Figure 6.3.

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of opening)

Heat & Glo • HST-42D • 27177 • Rev AB • 11/08