Venting – Harman Stove Company PF 100 User Manual

Page 12

background image

12

PF100

Requirements for Terminating the Venting

WARNING: Venting terminals must not be recessed

into a wall or siding.

NOTE: Only PL vent pipe wall pass-throughs and

fire stops should be used when venting through com-
bustible materials.

NOTE: Always take into consideration the effect

the prevailing wind direction or other wind currents will
cause with flyash and /or smoke when placing the termi-
nation.

In addition, the following must be observed:
A. The clearance above grade must be a minimum

of 18".

1

B. The clearance to a window or door that may

be opened must be a minimum of 48" to the side, 48"
below the window/door, and 12" above the window/
door.

1

(

with outside air installed, 18” )

C. A 12" clearance to a permanently closed win-

dow is recommended to prevent condensation on the
window.

D. The vertical clearance to a ventilated soffit lo-

cated above the terminal within a horizontal distance of
2 feet (60 cm) from the center-line of the terminal must
be a minimum of 18".

E. The clearance to an unventilated soffit must be

a minimum of 12".

F. The clearance to an outside corner is 11" from

center of pipe.

G. The clearance to an inside corner is 12".

H. A vent must not be installed within 3 feet (90

cm) above a gas meter/regulator assembly when mea-
sured from the horizontal center-line of the regulator.

1

I. The clearance to service regulator vent outlet

must be a minimum of 6 feet.

1

J. The clearance to a non-mechanical air supply

inlet to the building or the combustion air inlet to any
other appliance must be a minimum of 48”.

1

K. The clearance to a mechanical air supply inlet

must be a minimum of 10 feet.

1

(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a

paved driveway located on public property must be a
minimum of 7 feet.

1,2

M. The clearance under a veranda, porch, deck

or balcony must be a minimum of 12 inches.

1,3

NOTE: The clearance to vegetation and other

exterior combustibles such as mulch is 36” as measured

from the center of the outlet or cap. This 36” radius
continues to grade or a minimum of 7 feet below the
outlet.

1

Certain Canadian and or Local codes or regula-

tions may require different clearances.

2

A vent shall not terminate directly above a side-

walk or paved driveway which is located between two
single family dwellings and serves both dwellings.

3

Only permitted if veranda, porch, deck, or bal-

cony is fully open on a minimum of 2 sides beneath the
floor.

V

A

= Vent terminal

= Air supply inlet

Fixed

Closed

Openable

Openable

Fixed

Closed

Inside

Corner

Detail

= Area where terminal is not permitted

Fig. 20

NOTE: Where passage through a wall, or partition
of combustible construction is desired, the
installation shall conform to CAN/CSA-B365. (if in
Canada)

Venting