Installation procedure – haier AU282AHEAA User Manual

Page 9

background image

(2) Piping size

Gas pipe

15.88x1.0mm

Install the removed flare nuts to
the pipes to be connected, then
flare the pipes.

Liquid pipe

Gas pipe

9.52x0.8mm

19.05x1.0mm

Liquid pipe

9.52x0.8mm

(3) Limitations for one way piping length and vertical height difference.

Precautions for refrigerant piping

Do not twist or crush piping.
Be sure that no dust is mixed in piping.
Bend piping with as wide angle as possible.
Keep insulating both gas and liquid piping.
Check flare-connected area for gas leakage.

Connecting method (indoor unit)
Apply refrigerant oil at half union as large and flare nut.
To bend a pipe, give the roundness as possible not to crush
the pipe.
When connecting pipe, hold the pipe centre to centre then
screw nut on by hand, refer to Fig.
Be careful not to let foreign matters, such as sands enter
the pipe.

(4) Piping connection

Forced fastening without centering
may damage the threads and cause a
gas leakage.

Gas pipe

12.7x1.0mm

Liquid pipe

6.35x0.8mm

Pipe dia

Fastening torque

Liquid pipe 6.35mm

Gas pipe 15.88mm

Liquid pipe 9.52mm

Gas pipe 19.05mm

14.2-17.2N.m

61.8-75.4N.m

32.7-39.9N.m

97.2-118.6N.m

Gas pipe 12.7mm

49.5-60.3N.m

AU36NAIEAA
AU362AIEAA

AU48NAIEAA
AU60NAIEAA

Refrigerant piping

8

90+0.5

AU242AGEAA
AU282AHEAA
AU28NAHEAA

Installation Procedure

AU182AEEAA

Model

One way piping length

Vertical height difference

(between indoor and outdoor)

less than 30 m

AU362AIEAA AU36NAIEAA
AU48NAIEAA AU60NAIEAA

AU242AGEAA AU282AHEAA
AU28NAHEAA

less than 50 m

less than 15 m

less than 30 m

AU182AEEAA

less than 20 m

less than 10 m