Installation procedure, Air discharging method, Check if the pressure drops – haier AU282AHEAA User Manual

Page 10: Checking the leaking point, Refrigerant piping

background image

In the first to third test steps, if the pressure drops, check the leakage in each joint
use sense of hearing, feeling and soap water, etc. methods to find the leaking point.
After confirming the leaking point, welding it again or tighten the nut tightly again.

Checking the leaking point

First step: 0.3MPa (3.
0kg/cm

2

g) pressurize

over 3 minutes.

Second step: 1.5Mpa
(15kg/cm

2

g) pressurize

over 3 minutes. Large
leakage will be found.

Third step: 3.0 MPa
(30kg/cm

2

g) pressurize

about 24 hours. Little
leakage will be found.

After finishing connection of refrigerant pipe, it shall perform air tightness test.
The air tightness test adopts nitrogen tank to give pressure according to the pipe connection
mode as the following figure shown.
The gas and liquid valve are all in close state. In order to prevent the nitrogen entering the
circulation system of outdoor unit, tighten the valve rod before giving pressure (both gas
and liquid valve rods).

Outdoor

Completely tightened

Completely tightened

Flare part

Outdoor units

Manhole

Discharging valve

3-way valve totally closed
(Gas side)

Low pressure peizometer

High pressure peizometer

Meter separator

Dropping valve

3-way valve totally closed
(Liquid side)

Nitrogen tank

VL VH

Indoor units

Indoor

Flare part

9

From pressurizing to 24 hours later, each 1* difference of ambient temperature

will make 0.01MPa(0.1kg/cm

2

g) pressure change. It shall be corrected during test.

Check if the pressure drops

The pressure does not drop-passed
The pressure drops-check the leaking point.

5. Air discharging method

CYLINDER
OF
NITROGEN

SERVICE
HOUSE

LARGE
SLIP-ON
CONNECTOR

SWEAT
JOINT

TUBING
BRING
BRAZED

LINE
PRESSURE
GAUGE

CYLINDER
PRESSURE
GAUGE

Installation Procedure

Refrigerant piping