Installation procedure, Test run, Trouble display – haier AU282AHEAA User Manual

Page 14: Caution

background image

13

Electric wiring

6. Test run

CAUTION

THIS UNIT WILL BE STARTED INSTANTLY WITHOUT "ON" OPERATION
WHEN ELECTRIC POWER IS SUPPLIED.BE SURE TO EXECUTE "OFF"
OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR
SERVICING.

This unit has a function of automatic restart system after recovering power stoppage.

Installation Procedure

Failure description

Room temp. sensor abnormal

Indoor coil temp. sensor abnormal

Outdoor coil temp. sensor abnormal/
(compressor discharge temp. sensor)

Over-current malfunction/

power supply abnormal

Communication malfunction between indoor and wired controller
Communication malfunction between indoor and outdoor abnormal

Coil gas pipe temp. Sensor abnormal

Code on wired Flash times of indoor
controller receiver board
01 Power LED flashes 1 time
02 Power LED flashes 2 times
4A Power LED flashes 3 times
49 Power LED flashes 4 times

48 Power LED flashes 5 times
53

Power LED flashes 6 times

07 Power LED flashes 8 times
06 Power LED flashes 9 times

03 Power LED flashes 12 times

Outdoor temp. sensor abnormal

High / Low pressure abnormal

Temperature protection malfunction

0D Power LED flashes 13 times

Drainage system malfunction

08 Power LED flashes 10 times
0B Power LED flashes 11 times

Alarm of exterior annunciator

7. Trouble display

(1) Before starting test run (for all Heat pump models)

Confirm whether the power source breaker (main switch) of the unit has been
turned on for over 12 hrs to energize the crankcase heater in advance of operation.

(2) Test run

Run the unit continuously for about 30 minutes, and check the following.

Suction pressure at check joint of service valve for gas pipe.
Discharge pressure at check joint on the compressor discharge pipe.
Temperature difference between return air and supply air for indoor unit.

The following consults are according to the EMC testing.

Through

poor conditions of the electrical MAINS, shortly voltage drops can

appear when starting the EQUIPMENT. This can influence other

equipment

(eg. Blinking of a lamp ). But if the Mains-Impedance Zmax value can meet
the below chart, such

disturbances

are not expected. (In case of need, you may

contact your local supply authority for further information ).

Model

Zmax value

AU60NAIEAA

<0.2708OHM

AU48NAIEAA

AU282AHEAA AU362AIEAA

<0.2984OHM

<0.0741OHM

AU242AGEAA

<0.2721OHM

AU36NAIEAA

<0.2830OHM