SF2600 burner Set up

7”

12½”

7¾”

12⅞”

SF2600 Oil burner Setup
Nozzle

80

Degree

Solid

Cone

Off Cycle Damper Setting (B)

No.1 (as low as it goes

Flamelock

Setting

(A)

No.

1

Combustion Air (C)

No. 1 to 1¼

Draft - (Inches of water column)

.06 to .08

Tests for CO² must be made without a fire in the wood/ coal firebox, and with all doors and draft controls completely closed.

The burner should be fired for several minutes prior to taking a reading. Normal CO² reading is 11 to 12 with a stack

temperature of 300 degrees or less. This would give you an efficiency of 84 to 85 percent.