SF2600 burner Set up
7”
12½”
7¾”
12⅞”
SF2600 Oil burner Setup
Nozzle
80
Degree
Solid
Cone
Off Cycle Damper Setting (B)
No.1 (as low as it goes
Flamelock
Setting
(A)
No.
1
Combustion Air (C)
No. 1 to 1¼
Draft - (Inches of water column)
.06 to .08
Tests for CO² must be made without a fire in the wood/ coal firebox, and with all doors and draft controls completely closed.
The burner should be fired for several minutes prior to taking a reading. Normal CO² reading is 11 to 12 with a stack
temperature of 300 degrees or less. This would give you an efficiency of 84 to 85 percent.