OPERATION and MAINTENANCE - 
 
 
It is important that the two
previous sections of this installation 
booklet have been read and followed 
carefully before attempting to start up 
the equipment. 
 
 
A thorough inspection should be
made prior to start up to assure that 
there are no loose nuts, bolts, electrical 
connections or refrigeration lines 
rubbing or chafing. Turn the power 
switch to the ON position. ALLOW 
system to reach normal operating 
temp.prior to 
loading any 
product. 
This cabinet 
has a 
forced-air 
curtain that 
flows over the 
top of the 
product. 
 
 
 
 
 
See SHELVES for the special
loading instructions. Air flows out of the 
honeycomb diffuser located above the 
product, across the product, and into the 
return duct. The honeycomb can be 
removed for cleaning. 
 
TEMPERATURE CONTROL – 
 
Interior cabinet temperatures are
controlled through the use of a bulb and 
capillary type temperature control. The 
control is located in the electrical box. 
 
 
The sensing bulb is mounted on the
top of the evaporator coil on the 4060 and 
4072. On the 5272 it is located on the rear 
wall behind the evaporator coil. Be sure 
to disconnect power supply prior to any 
service work on the control. 
 
 
The control is factory pre-set
between 19º and 21ºF for the GSVM4060, 
4072 and - 26º to 28ºF on the GSVM5272 to 
maintain between 35º and 40ºF interior 
cabinet average temperatures. 
 
 
The differential is set at 8-10ºF or
alittle over halfway towards “MAX”. 
Donot adjust lower or evap. icing will 
occur. It can be adjusted to other desired 
temperatures by turning the dial to the 
corresponding dial face temperatures. The 
indicated dial temperature will not directly