HP Refrigerated Recirculating Chillers User Manual
Page 6
Notes: Refer to the serial number plate on rear of the chiller for model and electrical data.
Cooling Capacity, Watts x 3.41 = BTUs/hr. Performance specifications determined at ambient temperature of 20°C/68°F.
For 50Hz models, derate cooling capacity and pump flow by 17%.
External Pressure Reducing Assembly (for Positive Displacement Pump models) Steps down high outlet pressure to 10 to 45 psi. Cat. No 060302
6
6000 Series Standard Chillers with Magnetic Drive Centrifugal Pump
Model
6705
6105
6155
Operating Temperature
-15° to 40°C
-15° to 40°C
+5° to 35°C
Compressor
3/4 hp
1 hp
1
1
/
2
hp
Cooling Capacity
@20°C 2500 Watts
@20°C 2850 Watts
@20°C 5200 Watts
@10°C 1700 Watts
@10°C 1925 Watts
@10°C 3600 Watts
@ 0°C 760 Watts
@ 0°C 940 Watts
@ 5°C 2700 Watts
Pressure at 0 Flow Rate
10 psi
10 psi
10 psi
Flow Rate @ 0 psi
4.3 gpm / 16.3 lpm
4.3 gpm / 16.3 lpm
4.3 gpm / 16.3 lpm
Reservoir Capacity
1.65 gal / 6.25 liters
1.65 gal / 6.25 liters
6.25 gal / 23.65 liters
Dimensions (in.)
24 x 14
3
/
8
x 26
1
/
2
24 x 14
3
/
8
x 26
1
/
2
30 x 21x 27
h x w x d (cm)
61 x 36.5 x 67.3
61 x 36.5 x 67.3
76.2 x 53.3 x 68.6
Shipping Weight
178 lbs
178 lbs
450 lbs
Volts, Hz, Amps
208-230V, 60Hz, 7.5A
208-230V, 60Hz, 8A
208-230V, 60Hz, 12A
Volts Range
187V to 253V
187V to 253V
187V to 253V
60Hz Cat. No.
080531
080542
080593
Volts, Hz, Amps
240V, 50Hz, 7.5A
240V, 50Hz, 8.5A
240V, 50Hz, 12A
Volts Range
198V to 264V
198V to 264V
198V to 264V
Over Voltage: Category II
50Hz Cat. No.
080536
080546
080594
Additional Specifications for "P" Series 6000 Chillers with Positive Displacement Pump
Model "P" Series
6705P
6105P
6155P
Flow Rate @ 0 psi
4 gpm / 15.2 lpm
4 gpm / 15.2 lpm
4 gpm / 15.2 lpm
Pump Pressure (Adjustable)
20 to 100psi
20 to 100psi
20 to 100psi
Shipping Weight
178 lbs
178 lbs
450 lbs
Volts, Hz, Amps
208-230V, 60Hz, 10A
208-230V, 60Hz, 11A
208-230V, 60Hz, 12A
Volts Range
187V to 253V
187V to 253V
187V to 253V
60Hz Cat. No.
080532
080544
080596
Volts, Hz, Amps
240V, 50Hz, 10A
240V, 50Hz, 11A
240V, 50Hz, 12A
Volts Range
198V to 264V
198V to 264V
198V to 264V
Over Voltage: Category II
50Hz Cat. No.
080537
080547
080597
Additional Specifications for "T" Series 6000 Chillers with Turbine Pump
Model "T" Series
6705T
6105T
6155T
Flow Rate @ 0 PSI
3.5 gpm / 13.2 lpm
3.5 gpm / 13.2 lpm
3.5 gpm / 13.2 lpm
Pump Pressure (Adjustable)
20 to 100psi
20 to 100psi
20 to 100psi
Volts, Hz, Amps
208-230V, 60Hz, 9.6A
208-230V, 60Hz, 10.8A
208-230V, 60Hz, 12A
Volts Range
108V to 132V
108V to 132V
187V to 253V
60Hz Cat. No.
080533
080543
080598
Volts, Hz, Amps
240V, 50Hz, 9.6A
240V, 50Hz, 10.8A
240V, 50Hz, 12A
Volts Range
198V to 264V
198V to 264V
198V to 264V
Over Voltage: Category II
50Hz Cat. No.
080538
080548
080599
Environmental Conditions
• Indoor Use Only
• Maximum Altitude : 2000 meter
• Operating Ambient : 5° to 30°C
• Relative Humidity : 80% for temperatures to 30°C
• Pollution Degree : 2
• Class 1 : Residential, Commercial, Light Industrial
• Class 2 : Heavy Industrial