Safety precautions – haier AD52NAHBEA User Manual
Page 6
5
1. Applicable ambient temperature range:
The machine is adaptive in following situation
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent
or a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The power cable and connecting cable are self-provided. The power cable should be
H07RN-F 5G 4.0mm
2
(for AD52NAHBEA) or
H07RN-F 5G 2.5mm
2
(forAD28NAHBEA(380-400V, 3N~, 50Hz), AD36NAHBEA,
AD42NAHBEA) or
H05RN-F 3G 4.0mm
2
(for AD242AHBEA).
H05RN-F 3G 6.0mm
2
(for AD28NAHBEA(1PH, 220-230V~,50Hz)).
The connecting cable should be H05RN-F 4G 0.75mm
2
All the cables shall have got the European authentication certificate. During installa-
tion, when the connecting cables break off, it must be assured that the grouding wire is
the last one to be broken off.
6. The breaker of the air conditioner should be all-pole switch; and the distance between its
two contacts should be no less 3mm.
7. The indoor unit installation height is at least 2.5m.
Safety Precautions
Cooling
Heating
Indoor
outdoor
Rated Maximum Minimum
27 32 18
19 23 14
35 43 10
24 26 6
20 27 15
14.5 -- --
7 24 -7
6 18 --
DB C
WB C
DB C
WB C
Indoor
outdoor
DB C
WB C
DB C
WB C