Installation manual for indoor unit, Refrigerant pipe – haier AD52NAHBEA User Manual

Page 21

background image

20

11. Refrigerant pipe

[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause
water leakage.]

The outdoor unit has been charged with refrigerant.
When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown,
use spanner and torque spanner together.
When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use
hand to twist 3-4 rings, then fasten with spanner.

Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)
Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.
Only use seal cushion to bind the joint part of air pipe and heat insulation parts.

Paste the refrigerant oil here

Torque spanner

Spanner

Pipe joint

Cone nut

Middle size seal cushion (accessory)

(Use seal cushion to
bind the pipe joint)

Clamp

Heat insulation (accessory)

(for liquid pipe)

(for gas pipe)

Heat insulation (accessory)

Gas pipe

Liquid pipe

Liquid pipe

Gas pipe

Electric box

Upper

Air inlet

Air outlet

Down side

Drain hose connection mouth
VP25 PVC pipe

9.52

12.0~12.4

18.6~19.0

3270~3990 N.cm
(333~407 kgf.cm)

6180~7540 N.cm
(630~770 kgf.cm)

(mm)

Specification of pipe

15.88

Tighten torque

Cone

Cone dimension
A (mm)

R0.4~0.8

A

90 0.5

45 2

Installation Manual For Indoor Unit

22.9~23.3

9720~11860 N.cm
(990~1210 kgf.cm)

19.05

310

30

530

80

510