8. The attentive matters in installation of air suction and discharging duct

Recommend to use anti-frost and sound-absorbing
duct. (locally bought)
The duct installation work should be finished
before the fitment of ceiling.
The duct must be heat insulated.

The specific air-discharging outlet should be installed at
the place where the airflow can be reasonably distributed.
The surface should leave a checking meatus for checking
and maintenance.

9. The examples of improper installation

Do not use air in duct and take the ceiling inner side instead. The result is because of the irregular
outer air mass, strong wind and sunshine, the humidity is increased.

There may be water drop on the outside of duct. For cement and other new constructions, even if
not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber
to perform heat preservation to the whole. (use iron net to bind the glass fiber)

Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction,
when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow,
leading to water leakage.

Air

Air

Duct

Special air discharging outlet

Use screw bolt to fix

Air discharging fan

Improper example

Installation Manual For Indoor Unit