60-2553—3

6

EXAMPLE: Setpoint of 140

°F (60°C) differential set at

25

°F (14°C). On a temperature rise, R-B breaks and

R-W makes at 155

°F (68°C). On a temperature fall,

R-B makes and R-W breaks at 130

°F (54°C); see

Fig. 7.

L8151A

OPERATION AND SETTINGS • CHECKOUT

THERMOSTAT ANTICIPATOR

Set the thermostat heat anticipator at 0.2A.

Checkout

Put the system into operation and observe each function through at least one complete cycle. Be sure the control operates

as intended.