beautypg.com

Power up, Fig. 6 a, Fig. 6 – Honeywell ZIO TR75 User Manual

Page 4: Setting the wall module bus address dial, Attaching the wall module to the subbase, Removing the wall module from subbase, Automation and control solutions, Please load

background image

ZIO

®

/ZIO PLUS LCD WALL MODULES

Automation and Control Solutions

Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com

® U.S. Registered Trademark
© 2012 Honeywell International Inc.
62-0271—07 M.S. Rev. 01-12
Printed in United States

Fig. 6. Terminal connections, Wall Module bus address

dial, and TR70-H address dial (rear view of LCD wall

module).

Setting the Wall Module Bus Address Dial

For the TR70, ensure that the wall module bus address dial is

set to 1. For the TR71 or TR75 models, set the address to any

number from 0 to 9. (A setting of 0 on Zio is equal to 10 in the

Configuration Tool, so if the Zio is set to 0, set the address to

10 in the Configuration Tool.) Address must be different for

each device on the Sylk bus. Use a thin blade screwdriver to

turn the dial arrow. The address on the wall module must

match the address in the tool. A maximum of four Zios may

be wired on a single Sylk bus, with no more than one TR70

per bus.

Attaching the Wall Module to the Subbase

When all wiring is complete, press the LCD wall module

straight down onto the subbase until it snaps into place.

Removing the Wall Module from Subbase

To remove the wall module from its subbase:

1. Insert a thin, flat-blade screwdriver into the slot on the

right side of the wall module (see Fig. 7).

2. Pull the screwdriver toward you to release the right side

of the wall module from the subbase.

3. Pull the wall module out and away from the subbase.

Fig. 7. Removing Wall Module from Subbase.

POWER UP

After the wall module is properly wired to the controller, it will

power up. Upon initial power up, the wall module LCD panel

displays the phrase,

“PLEASE LOAd”

(see Fig. 8). This

phrase alternates with bus address, model and version

number (TR71 and TR75 only), and any onboard sensor

display, such as temperature, humidity, etc.

Refer to the Zio/Zio Plus LCD Wall Modules Operating Guide

(Form 63-2719) to configure and load the desired user

interface and parameters into the wall module.

Fig. 8. Wall Module LCD display at initial power up.

ComfortPoint™ is a trademark of Honeywell International Inc.

L

ON

M

ARK

® is a trademark of the LonMark Association.

BACnet® is a trademark of BACnet International.

Sylk® is a trademark of Honeywell International Inc.

Zio® is a trademark of Honeywell International Inc.

M27349

SLOTS FOR SUBBASE

LOCKING TABS (X4)

0

1 2 3

4

9

8 7 6

5

WALL MODULE BUS

ADDRESS DIAL

(DEFAULT SETTING = 1)

S-BUS PROGRAMMABLE

CONTROLLER CONNECTION

NETWORK BUS

CONNECTION

EACH OF THE TWO WIRE CONNECTIONS FOR THE S-BUS AND NETWORK

BUS TERMINALS ARE POLARITY INSENSITIVE.

1 2 3 4

1

1

50028668-XXX

4

3

2

1

S-BUS

S-BUS

NET-2

(optional)

NET-1

(optional)

TR70-H

YY WK

HONEYWELL

PATENT PENDING

GOLDEN VALLEY,MN

ASSEMBLED IN MEXICO

WALL

PULL THE

SCREWDRIVER

TOWARD YOU

M27350

M27351A

This manual is related to the following products: