Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

3

68-0282—07

W8150 QUICK GUIDE

No.

Name

Description

Function

1

G

F

Equipment fan

Allows W8150 to pass thermostat calls and, when necessary, turn on

system fan for ventilation. This should be the only connection to G on the

HVAC equipment.

2

R

C

24 Vac cooling system

power

Provides power to G

F

terminal to operate system fan, when necessary.

3

C

C

24 Vac cooling system

common

Allows W8150 to monitor when system fan is energized.

4

C

H

24 Vac heating system

common

Allows W8150 to monitor thermostat heat calls when W is energized.

5

W

Heating

Allows W8150 to monitor when heating is energized.

6

G

T

Thermostat (or other

control) fan terminal

Allows W8150 to monitor when G

T

is energized. All external equipment that

controls the system fan should be wired to this terminal.

7

Switch

On (optimal ventilation)

Override

Off (Remote Only)

On (optimal ventilation) – W8150 ventilates, based on control settings.

Override – W8150 runs ventilation continuously.

Off (Remote Only) – W8150 supplies ventilation only when there is a

remote call.

8

Light

Green

Indicates device is powered and operating normally. Used in Test Mode to

signal if dial settings meet chosen standard.

9

Light

Red

Indicates the device is not operating normally. Used in Test Mode to signal

if dial settings do not meet chosen standard.

10

DIP1

Ventilation limit

Choose between 60% (default) and 100% maximum fan run time allowed

by W8150 for ventilation.

11

DIP2

Ventilation standard

Choose between ASHRAE 62.2 (default) and 62-1999 ventilation

standards.

12

BEDROOMS

Number of bedrooms

Used to calculate amount of ventilation necessary.

13

AREA

(SQ FT)

Square footage of

conditioned space

Used to calculate amount of ventilation necessary.

14

VENT

AIRFLOW

(CFM)

Air delivery rate through

fresh air duct.

Used to calculate amount of ventilation necessary.

15

Test

Test button

W8150 checks dial and switch settings, activates ventilation for up to three

minutes and provides feedback to validate if chosen standard can be met.

ON

BEDROOMS

AREA (SQFT)

VENT AIRFLOW (CFM)

REMOTE

A

UX

DAMPER

C

R

G

F

R

C

C

C

C

H

W

G

T

XFMR

1

2

3

4

5

6

7

8

9

13

M19990

14

11

12

10

15

16

17

18

19

20