beautypg.com

Specifications: m7215 – Honeywell M8405 User Manual

Page 4

background image

SOLID STATE ECONOMIZER SYSTEM

63-2484—2

4

Fig. 2. Approximate dimensions of C7150B Mixed/

Discharge Air Sensor in in. (mm).

Fig. 3. Approximate dimensions of C7400A Solid State

Enthalpy Sensor/C7650A Solid State Temperature Sensor

in in. (mm).

M7415A, M8405A Damper Actuators

Provides control of economizer systems on HVAC equipment.

Actuator Rotation:

Closed position is the limit of clockwise rotation; open position

is the limit of counterclockwise rotation as viewed from the

shaft end of the motor.

Auxiliary Switch Rating (M8405A only):

24 Vac, 20 VA inrush, 20 VA run.

Terminal Connections:

1/4 in. (6 mm) male quick connect terminals mounted on actua-

tor. Terminal arrangement is dependent on actuator model.

Ambient Operating Temperature Range:

-40°F to +125°F (-40°C to +52°C).

Voltage and Timing:

See Table 1.

Dimensions:

See Fig. 4.

Shaft:

Single-ended drive shaft with crank arm supplied.

Flammability Rating:

Underwriters Laboratories Inc. UL94-5V.

Approval:

Underwriters Laboratories Inc. Component Recognized: File

No. E4436, Guide No. XAPX2, Vol. 9, Section 1, 7-25-83.

SPECIFICATIONS: M7215

Models: ML7215: 25 lb-in. (2.8 Nm) torque, foot-mounted

spring-return damper motor with 2-10 Vdc feedback signal.

Accepts 2-10 Vdc control signal.

Dimensions: See Fig. 4.

Electrical Ratings:

Supply Voltage: 24 ±6 Vac 50/60 Hz.

Power Consumption: 24 Vac, 60 Hz: 8.7 VA. 24 Vac, 50 Hz: 8.4

VA.

Torque:

Lift and Hold: 25 lb-in. (2.8 Nm). Spring Return: 25 lb-in. (2.8

Nm). Breakaway: 40 lb-in. (4.5 Nm).

IMPORTANT

Never use motor continuously at the breakaway

torque rating.

NOTE: Breakaway torque available to overcome occasional

large loads such as a seized damper.

Stroke:

Travel: 90°.

Timing:

Driving: 86 ±5 seconds.

Spring Return: 13 ±5 seconds.

Motor Rotation (Viewed From Shaft End):

Closed Position: Limit of clockwise rotation.

Open Position: Limit of counterclockwise rotation.

Crank Arm Rotation Limits: See Fig. 8.

Shipped with shaft in closed position.

Ambient Ratings:

Temperature:

Operating: -25°F to +125°F (-32°C to +52°C).

Storage: -30°F to +150°F (-34°C to +66°C).

Humidity: 5 to 95 percent RH, noncondensing.

Terminal Connections: 1/4 in. (6 mm) quick-connect termi-

nals mounted on motor.

3/16 (5) DIAMETER

2-1/2 (64)

2

(51)

3/4

(19)

M9084

M9096

S

+

9/16

(14)

3-7/8 (96)

5/16 (8)

3-5/32

(80)

2-3/4

(70)

1 (25)

7/32

(6)

This manual is related to the following products: