Solid state economizer system – Honeywell M8405 User Manual

Page 22

background image

SOLID STATE ECONOMIZER SYSTEM

63-2484—2

22

Fig. 29. W7212 used with M7215 Damper Motor and T7300 Thermostat.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR. USE THE SAME

TRANSFORMER FOR T7300 AND ECONOMIZER.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE

WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.

T7300 TERMINALS A1 AND A2 ARE CONNECTED WHEN THERMOSTAT IS IN THE OCCUPIED MODE.

EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.

M20716D

S

1

2

3

2

+

4

5

5

C7400

OUTDOOR

AIR

ENTHALPY

SENSOR

L1

(HOT)

L2

FAN

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENT

TERMINAL STRIP

T7300/Q7300

THERMOSTAT

1

C

G

W1

A2

A1

Y1

Y2

R

W2

RC

RH

G

X

W1

Y1

Y2

W2

A1

A2

COOL 2

N1

P1

T1

SR

SO

AQ

EF1

EXHAUST

FAN

L1

(HOT)

L2

4

EF

3

5

2

1

TR

MINIMUM POSITION

ADJUSTMENT

P

T

AQ1

SO+

SR+

TR1

24 Vac

COM

24 VAC COM

24

Vac

HOT

2-10 VDC CONTROL

+

3

620 OHM

RESISTOR

C7150B MIXED

AIR OR C7046A

DISCHARGE

AIR SENSOR

+

0/2-10 VDC

INDOOR AIR

SENSOR

N

4

24 VAC HOT

SIGNAL INPUT

W7212

M7215