SOLID STATE ECONOMIZER SYSTEM

27

63-2484—2

Fig. 34. W7212 controlling parallel-wired Honeywell Series 72 Actuators and time clock for occupancy.

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

ENSURE THAT TRANSFORMER IS SIZED TO HANDLE

THE LOAD OF ALL ACTUATORS.

USE THE FOLLOWING CONTACTS INSTEAD OF TIMER

FOR T7300, USE A1 AND A2 TERMINALS.

FOR T7350 USE AUX TERMINAL.

FOR TB7220 OR TB8220 USE A TERMINAL

THE TERMINALS ARE CONNECTED WHEN THERMOSTAT

IS IN THE OCCUPIED MODE.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR

SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY

SENSOR IS ADDED TO SR AND SR+ FOR DIFFERENTIAL

ENTHALPY.

EF AND EF1 ARE DRY CONTACTS IN THE

LOGIC MODULE.

SEE WIRING DIAGRAMS FOR T7350

AND TB7220/TB8220.

TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS

ON THE THERMOSTAT.

M24221

1

2

3

4

5

ST6008

TIMER

1

2

L1

(HOT)

L2

L1

(HOT)

L2

L1

(HOT)

L2

FDR

FDR

FAN

HEAT 1

HEAT 2

COOL 1

COOL 2

HVAC EQUIPMENT

TERMINAL STRIP

THERMOSTAT

1

C

G

W1

Y1

Y2

R

W2

RC

G

X

W1

RH

Y1

Y2

W2

3

FAN

DELAY

RELAY

S

+

C7400

OUTDOOR

AIR

ENTHALPY

SENSOR

N1

P1

T1

SR

SO

AQ

EF1

4

EF

3

5

2

1

TR

MINIMUM POSITION

ADJUSTMENT

P

T

AQ1

SO+

SR+

TR1

24 Vac

COM

24

Vac

HOT

+

4

5

620 OHM

RESISTOR

W7212

C7150B MIXED

AIR OR C7046A

DISCHARGE

AIR SENSOR

+

0/2-10 VDC

INDOOR AIR

SENSOR

N

UNOCCUPIED

OCCUPIED

1

EXHAUST

FAN

L1

(HOT)

L2

F

1
2
3
4
5

+

~

MS7XXX

HONEYWELL

ACTUATOR

F

1
2
3
4
5

+

~

MS7XXX

HONEYWELL

ACTUATOR

6

7

6

7