Sil 2/3 compliance – Honeywell STR12D User Manual

Page 10

background image

34-ST-03-64

Page 10

Performance Under Rated Conditions * - Model STR14A (0-5 to 0-500 psia)

Parameter

Description

Upper Range Limit **

psia

bar

absolute

500

35

Minimum Span

psia

bar

absolute

5

0.35

Turndown Ratio

100 to 1

Zero Elevation and Suppression No limit except minimum span from 0 to 100% URL.

Accuracy

(Reference – Includes

combined effects of linearity,
hysteresis, and repeatability)

Accuracy includes residual error

after averaging successive
readings.

For F

OUNDATION

Fieldbus use

Digital Mode specifications. For
HART use Analog Mode
specifications.

In Analog Mode:

±0.1% of calibrated span or upper range value (URV), whichever is

greater.
For URV below reference point (20 psi), accuracy equals:

±0.05 + 0.05

(

)

20 psi

span psi

or ±0.05 + 0.05

(

)

1.4 bar

span bar in % of span

In Digital Mode:

±0.075% of calibrated span or upper range value (URV), whichever is

greater.
For URV below reference point (20 psi), accuracy equals:

±0.025 + 0.05

(

)

20 psi

span psi

or ±0.025 + 0.05

(

)

1.4 bar

span bar in % of span

* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.

** Transmitter URL limit or maximum seal pressure rating, whichever is lower.


Performance Under Rated Conditions – General for all Models

Parameter

Description

Output (two-wire)

Analog 4 to 20 mA or digital communications DE mode. Options available for

F

OUNDATION

Fieldbus and HART protocol.

Supply Voltage Effect

±0.005% of span per volt.

Damping Time Constant

Adjustable from 0 to 32 seconds digital damping.

RFI Protection (Standard)

Negligible (20 to 1000 MHz at 30 volts per meter).

CE Conformity (Europe)

89/336/EEC, Electromagnetic Compatibility (EMC) Directive.

NAMUR NE 43 Compliance

Option

Transmitter failure information is generated when the measuring information is invalid or

no longer present. Failure information is transmitted as a current signal but outside the

normal 4-20 mA measurement signal level. Transmitter failure values are: ≤ 3.6 mA and
≥ 21.0 mA. The normal signal range is ≥ 3.8 mA and ≤ 20.5 mA.

SIL 2/3 Compliance

SIL certified to IEC 61508 for non-redundant use in SIL 2 related Safety Systems

(single use) and for redundant (multiple) use in SIL 3 Safety Systems through

TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 1998;

IEC 61508-2: 2000; IEC61508-3: 1998.