19

5. Electrical Connection

WARNING

1. Electrical connection must meet national, state, and local electrical code

requirements. Failure to meet these code requirements could result in
death,electric shock, serious injury, fire, or extensive damage to equipment.

2.

THIS UNIT MUST BE GROUNDED. Be sure to install a proper ground from

the icemaker to the remote condenser unit. Use wire of an appropriate gage
and outdoor rating. Failure to properly ground this unit could result in death
or serious injury.

3. The remote condenser unit must be connected to the fan motor junction box

on the icemaker. Use wire of an appropriate gage and outdoor rating. Do not
connect the remote condenser leads to an external power source.

4. To reduce the risk of electric shock, make all remote condenser unit

connections before connecting the icemaker power supply.

5. On remote air-cooled model, the icemaker should have power for a minimum

of 4 hours prior to startup to prevent compressor damage.

• Usually an electrical permit and services of a licensed electrician are required.
• The opening for the power supply connection is 7/8" DIA to fit a 1/2" trade size conduit.

1) Remove the louver panel. See Fig. 14.
2) Remove the junction box cover on the remote condenser unit. Remove the fan motor

junction box cover on the icemaker.

3) Install a ground wire from the icemaker to the remote condenser unit. Use wire of an

appropriate gage and outdoor rating.

4) Connect the fan motor leads in the junction box of the remote condenser unit to the fan

motor leads in the fan motor junction box of the icemaker.

5) Replace the junction box covers and the louver panel in their correct positions.

Fig. 14

Screws

Louver Panel

Junction Box
Cover

Remote Condenser Unit

Icemaker

Screw

Fan Motor Junction
Box Cover