Series 185

CONTROLLER

(continued)

4

381333–319 D

S2 DIP switch

S1 DIP switch

Figure 6. DIP switches S1 and S2 at the top right.

The time delay settings are shown in Figures 6 and 7 and
in Table C. The sensor settings are shown in Figure 6
and in Table D. The standard (factory) settings are
shown in Tables C, D, and H.

S3 DIP switch

Figure 7. DIP switch S3 at the bottom center.

Table C. Time Delay Settings

Time Delay Description

Factory Setting

Settings

DIP Switch

DIP Actuator

Actuator Position

override momentary

3 seconds

1 second

S2

1

on (up)

override momentary

utility outages

3 seconds

3 seconds

S2

1

off (down)

transfer to generator

10 seconds (approx.)

override momentary

4 seconds

4 second

S3

9

on (up)

override momentary

generator outages

4 seconds

0

S3

9

off (down)

transfer to utility

5 minutes (approx.)

unloaded running

2 minutes

2 minutes

S1

10

on (up)

unloaded running

(generator cooldown)

2 minutes

5 minutes

S1

10

off (down)

Table D. Voltage and Frequency Settings

Setting Description

Setting

Factory Setting

Settings

DIP Switch

DIP Actuator

Actuator Position

voltage

220 – 240 V

non–adjustable

S2

2

on (up)

frequency

nominal

60 Hz

50 Hz

S1

4

on (up)

frequency

nominal

60 Hz

60 Hz

S1

4

off (down)

phase

single

non–adjustable

S1

6

on (up)

pickup

198 V

198 V

S1

3

on (up)

pickup

198 V

209 V *

S1

3

off (down)

198 V *

S1

1

off (down)

198 V *

S1

2

off (down)

utility voltage

187 V

S1

1

on (up)

utility voltage

dropout

187 V

187 V

S1

2

off (down)

dropout

187 V

176 V

S1

1

off (down)

176 V

S1

2

on (up)

154 V

S1

1

on (up)

154 V

S1

2

on (up)

generator voltage

pickup

198 V

non–adjustable

generator voltage

dropout

165 V

non–adjustable

generator frequency

pickup

57 Hz (nom 60 Hz)

48 Hz (nom 50 Hz)

non–adjustable

dropout

51 Hz (nom 60 Hz)

43 Hz (nom 50 Hz)

non–adjustable

* If the dropout voltage is set to 198 V, the pickup voltage must be set to 209 V.