3 --- Generator Starting Contacts

The generator starting contacts connections are on the
controller. Refer to the generator manual. Disconnect
the generator battery and verify that the ignition switch is
in the OFF position. Connect the generator starting
wires to the appropriate terminals on terminal block TB7
as shown on the wiring diagram. For wiring convenience
terminal block TB7 has a removable plug. See Figure 4
and Table A.

TB7

removable

terminal block

TB7–4, TB7–5, TB7–6

1 2 3 4 5 6 7 8 9

Figure 4. TB7 generator starting contact terminals.

Table A. Generator Start Connections

When the Utility fails

Terminals on Controller

contact closes

TB7–4 and TB7–5

contact opens

TB7–5 and TB7–6

4 --- Settings

The time delay and sensor setting in the Group 4
controller are accessible on the inside. Refer to Tables B
and C and to Figures 6 and 7. Use a ball–point pen or
other pointed tool to slide the DIP switch actuators up or
down to match setting shown.
All power must be off before making any changes.
The factory default settings are shown in Table G on
page 5.

screw

cover must be removed

to replace 9V battery

(use alkaline type)

Figure 5. Battery replacement.

5 --- Automatic Generator Exerciser

The built–in automatic generator exerciser can be set to
exercise the generator for 20 minutes once every week.

Clock Battery

Be sure a fresh battery is installed and turned on. It will
maintain the exerciser clock for about 24 hours in case of
a power outage.
Recommended 9 volt alkaline batteries are (see Figure
5): Duracell MN 1404, Everready 522, Panasonic 6AM6
Turn on battery by putting S2 DIP switch actuator 10 in
the on position (up). See Table B and Figure 6.

Exercise with or without Load

The generator should be exercised under load or follow
the recommendations of the generator manufacturer. Be
sure the exerciser is turned on. Then select either
exercise with or without load. The ATS will transfer the
load to the generator when the exercise with load is
selected. See Figure 6 and Table B.

Table B. Generator Exercise Settings

Function

Factory

Setting

DIP

Switch

DIP

Actuator

Actuator

Position

clock

battery

off

S2

10

on (up)

off (down)

exerciser

off

S1

7

on (up)

off (down)

with load or

without load

without

load

S1

8

with (up)

without (down)

To Set Exerciser

Press and hold (5 seconds) the Set Engine Exerciser
button. The exercise period occurs immediately and at
approximately the same time weekly thereafter. The
status light below the button blinks during the exercise
period (including the cooldown). The light stays on to
indicate that the exerciser has been set. If the light is off,
the exerciser has not been set.

To Cancel an Active Exercise Period

Press the Bypass Time Delay button to stop an exercising
generator. If exercise with load is set, the ATS
retransfers the load to the utility, then stops the
generator after cooldown.