Specifications

Wiring Specifications

Ordering Information

Power

24VAC ±10%, 50 to 60Hz, 24VA, or 26VDC ±10%, 10W, 48VDC

Dimensions

W x D x H: in. (mm)

Module: 11.3 x 0.56 x 7.5 (287 x 14.2 x 190.5)

Enclosure (brushed aluminum): 14.25 x 2.85 x 12 (362 x 72.4 x 304.8)

Communication Ports
• Ethernet Port

10/100Base-T Fast Ethernet port.

• ARC156 Port

ARCNET156 or EIA-485 communication. In ARCNET156 mode, the port communicates via

BACnet ARC156.

• TPI Port S1

EIA-232/422/485 configurable port for interaction with 3rd-party building automation systems

via software-selectable protocols. May also be configured for remote modem access.

EIA-422/485

Ports 1-12 - for

communication with

equipment via

software-selectable

protocols & baud

rates

Each port can be individually set for different protocols & baud rates.

The number of ports varies by model:
SiteLink-2E (SSW-2E)

SiteLink-4E (SSW-4E)

SiteLink-12E (SSW-12E)

Ports 11-12

These two ports include

an option for EIA-232

connection.

Ports 9-12

These four ports include

an option for EIA-232

connection.

Ports 1-12

Four of these 12 ports (9-12)

include an option for EIA-232

connection.

Environmental

Operating Range

20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing

Note: Control modules should be installed within the building.

Memory

16 MByte non-volatile battery-backed SDRAM and 8 MByte Flash

Protection

Built-in surge and transient protection circuitry - internal solid state polyswitches on incoming

power and network communications connections

Battery

3V lithium battery P/N CR-123A; battery shelf life is 10 years with 720 hours of continuous operation

Fault Detection

Hardware watchdog timer

Agency Listings

UL, cUL, CE, FCC

Connection

Supported Wire Types

Maximum Wire Length

Rating

Ethernet 10 BaseT

CAT 5

328 ft. (100m)

N/A

BACnet Port

MAGNUM Cable P/N A3-ARC-156-2

3000 ft. (915m)

N/A

Port S1 EIA-485

18-22 AWG Stranded & Shielded; 18 AWG (recommended)

Non Plenum - Belden 9461; Plenum - Belden 88761

1000 ft. (300m)

N/A

Port S1 EIA-232

18-22 AWG Stranded & Shielded; 18 AWG (recommended)

Non Plenum - Belden 9461; Plenum - Belden 88761

50 ft. (15m)

N/A

Quantity

Part #

Description

SSW-12E

SiteLink-12E with enclosure - communicates with up to 12 Liebert unit controllers

SSW-12EWO

SiteLink-12E without enclosure - communicates with up to 12 Liebert unit controllers

SSW-4E

SiteLink-4E with enclosure - communicates with up to 4 Liebert unit controllers

SSW-4EWO

SiteLink-4E without enclosure - communicates with up to 4 Liebert unit controllers

SSW-2E

SiteLink-2E with enclosure - communicates with up to 2 Liebert unit controllers

SSW-2EWO

SiteLink-2E without enclosure - communicates with up to 2 Liebert unit controllers