Eaton Electrical 10000L(XL) User Manual

Page 6

background image

4

Electrical performance

Input

Model

Voltage

Frequency

Power Factor

6000L(XL)/

10000L(XL)

Single-phase

(46~54)/(56~64)Hz

>0.98 (Full load)

Operating environment

Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following :

Output

Voltage

regulation

Power

factor

Frequency

tolerance

Distortion Overload capacity

Current

crest ratio

±

4%

0.7lag

Synchronized
(46~54)/(56~64)Hz
in Line mode(AC
mode)

±

0.1% of normal

frequency in
Battery mode.

THD<3%

Full load

(linear

load)

105%~130% load
transfers to bypass
mode after 10
minutes.

>130% load transfers
to bypass mode after
1 second and
shutdown the output
after 1 minutes

3:1

maximum

Temperature

Humidity

Altitude

Storage temperature

0℃~40℃

<95%

<1000m

-15℃~40℃

Altitude (M)

1000

1500 2000 2500 3000 3500 4000 4500 5000

Deratingpower 100% 95% 91% 86% 82% 78% 74% 70% 67%