beautypg.com

Emerson Liebert STS2 User Manual

Page 4

background image

4

Optimized Transfer Option Enhances
Cost-Efficient System Operation

Liebert offers a patented optimized transfer option for the Liebert STS2 that greatly

improves operation when used in primary side switching applications.

See also

White Paper “STS2

Optimized Transfer

(June 4, 2004)” at

www.liebert.com.

The Liebert STS2 can be used in two different types of high-availability dual bus

configurations—as primary or secondary side switches. For primary side switching,

the unit is connected to the primary or input of a downstream transformer. On

secondary side switching the Liebert STS2 is connected to the secondary or output of

two transformers.

One of the main advantages of using primary side switching is lower cost.

These savings are the result of only one power distribution unit, a lower current due

to 480V vs. 208V, and lower installation and wiring cost thanks to use of smaller three

wire cable.

The one drawback of this configuration is the creation of transformer inrush

saturation current each time switching occurs. The downstream transformer can

cause large peak saturation current during automatic transfers. The transformer

saturation is caused by DC-flux built-up during transfer, especially when the sources

are not in phase.

Figures 1 and 2

show results for the

standard STS2 vs.

the optimized STS2

for the same

condition

(alternate source

lags 120 degrees)

respectively. The

optimized transfer

control algorithm

minimizes the

transformer

saturation current

resulting from an

out of phase

transfer.

load voltages

Figure 1 Standard STS2 transfer

transformer fluxes

primary currents