Important safety requirements, An air vent of effective area of 110 cm, And 10 m – Electrolux 69802 G User Manual

Page 12: An air vent of effective area of 50 cm, Is required, while if the volume exceeds 11 m, And 11 m

background image

12

BURNER

RAPID

SEMI-RAPID

AUXILIARY

(large)

(medium)

(small)

POSITION

MAX

MIN

MAX

MIN

MAX

MIN

NOMINAL THERMAL
POWER kW

2.9

0.65

1.9

0.45

1.0

0.33

NOMINAL FLOW
RATE m

3

/h

0.276

0.062

0.181

0.043

0.095

0.031

NOZZLE REFERENCE

119

Adjust.

96

Adjust.

70

Adjust.

1/100 mm

NOMINAL THERMAL
POWER kW

2.7

0.65

1.9

0.45

1.0

0.33

NOMINAL FLOW
RATE g/h

195

46.8

137

32.4

72

23.8

NOZZLE REFERENCE

86

40

71

32

50

28

1/100 mm

NATURAL GAS

20 mbar
VALUE =

37.78 MJ/m

3

Ws - 50.7 MJ/ m

3

TYPE OF GAS

LPG GAS

28-30/37 mbar

VALUE =

49.92 MJ/Kg

Important safety requirements

This hob must be installed in accordance with the Gas Safety (Installation and

Use) Regulations (Current Edition) and the IEE Wiring Regulations (Current

Edition).
Detailed recommendations are contained in the following British Standards

Codes Of Practice: B.S. 6172/ B.S. 5440, Par. 2 and B.S. 6891 Current

Editions.
The hob should not be installed in a bed sitting room with a volume of less

than 20 m

3

. If it is installed in a room of volume less than 5 m

3

an air vent of

effective area of 110 cm

2

is required. If it is installed in a room of volume

between 5 m

3

and 10 m

3

an air vent of effective area of 50 cm

2

is required,

while if the volume exceeds 11 m

3

no air is required.

However, if the room has a door which opens directly to the outside no air vent

is required even if the volume is between 5 m

3

and 11 m

3

.

If there are other fuel burning appliances in the same room, B.S. 5440 Part 2

Current Edition, should be consulted to determine the requisite air vent

requirements.