Constructing a bus cable for profibus dp, 5 constructing a bus cable for profibus dp – ProSoft Technology 5104-DNPS-PDPM User Manual
Page 61

PDPM ♦ ProLinx Gateway
Reference
PROFIBUS DP Master
Protocol Manual
ProSoft Technology, Inc.
Page 61 of 70
June 24, 2013
Service
PROFIBUS
Version
Master Class 1
Master Class 2
Request
Response
Request
Response
DDLM_Data-Exchange
DPV0
Yes
No
DDLM_Set_Prm
DPV0
Yes
No
DDLM_Chk_cfg
DPV0
Yes
No
DDLM Slave Diag
DPV0
Yes
No
DDLM_Global_Control
DPV0
Yes
No
DDLM_Get_Cfg
DPV0
Yes
DDLM_Set_Slave_Add
DPV0
Yes
DDLM_Read_Input
DPV0
No
DDLM_Read_Output
DPV0
No
DDLM_Get_Master_Diag
DPV0
Yes
DDLM_Start_Seq
DPV0
No
No
DDLM_Download
DPV0
No
No
DDLM_Upload
DPV0
No
No
DDLM_End_Seq
DPV0
No
No
DDLM_Act_Param_Brct
DPV0
No
No
DDLM_Act_Param
DPV0
No
No
6.5
Constructing a Bus Cable for PROFIBUS DP
The bus cable for connecting PROFIBUS DP devices must be constructed by the
user. A special PROFIBUS cable (twisted pair) is required here. This standard
cable is available from various manufacturers and is a Belden part number
3079A.
If you plan to construct your own bus cable, the following part numbers are
provided for your convenience.
PROFIBUS connector: Siemens part number 6ES7972-0BA40-0XA0
PROFIBUS cable: Belden part number 3079A.
To construct the cable, proceed as follows:
1 Cut the cable to the required length.
2 Prepare the cable ends as shown in the illustration (dimensions in mm):