ProSoft Technology 5104-DNPS-PDPM User Manual
Page 22

Configuration
PDPM ♦ ProLinx Gateway
Protocol Manual
PROFIBUS DP Master
Page 22 of 70
ProSoft Technology, Inc.
June 24, 2013
Parameter Data Structure
SPC3 evaluates the first seven data bytes (without user prm data), or the first
eight data bytes (with user prm data). The first seven bytes are specified
according to the standard. The eighth byte is used for SPC3-specific
communications. The additional bytes are available to the application.
Byte
Bit Position
Designation
7
6
5
4
3
2
1
0
0
Lock
Reg
Unio
Req
Sync
Req
Free
Req
WD
on
Res
Res
Res
Station status
1
WD_Fact_1
2
WD_Fact_2
3
MinTSDR
4
Ident_Number_High
5
Ident_Number_Low
6
Group_Ident
7
Spec_User_Prm_Byte
8 to
243
User_Prm_Data
Byte 7
Spec_User_Prm_Byte
Bit
Name
Significance
Default State
0
Dis_Startbit
The start bit monitoring in the
receiver is switched off with
this bit
Dis_Startbit = 1,
That is, start bit monitoring is
switched off.
1
Dis_Stopbit
Stop bit monitoring in the
receiver is switched off with
this bit
Dis_Stopbit = 0
That is, stop bit monitoring is not
switched off.
2
WD_Base
This bit specifies the time
base used to clock the
watchdog.
WD_Base = 0: time base 10
ms
WD_Base = 1: time base 1 ms
WD_Base = 0
That is, the time base is 10 ms.
3 to 4
Res
To be parameterized with 0
0
5
Publisher_Enable
DXB-publisher-functionality of
the SPC3 is activated with this
bit
Publisher_Enable = 0, DXB-
request-telegrams are ignored;
Publisher_Enable = 1, DXB-
request-telegramme are processed
6 to 7
Res
To be parameterized with 0
0