Viewing the current configuration, Saving the current configuration, Configuring the an-x module in rslogix 5000 – ProSoft Technology AN-X2-SQD User Manual
Page 30

Page
24
AN-X2-SQD-MAS
June 2013
DataOutput ; Outputs from ControlLogix
0 d8s02 ; 0->0 ( 1) "ROM221 16 OUT AC"
1 d8s03 ; 1->1 ( 1) "ROM221 16 OUT AC"
2 d8s04 ; 2->2 ( 1) "ROM221 16 OUT AC"
3 d8s09 ; 3->6 ( 4) "ROM121 4 OUT ANLG"
Viewing the Current Configuration
To view the ControlLogix configuration currently stored in the AN-X, start the web
interface and select View Active Configuration.
Click the Ethernet/IP link to view the current ControlLogix scheduled data configuration.
Each line begins with a line number, from the original ControlLogix configuration file.
Each mapping line shows the offset and length of the data in the ControlLogix data
connection.
Saving the Current Configuration
To save the ControlLogix configuration currently stored in the AN-X to a file, start the
web interface and select Automation Network/View Active Configuration.
Right click the Ethernet/IP link and select Save target to save the current ControlLogix
scheduled data configuration to a file.
You can also save the ControlLogix configuration by selecting Automation Network/View
Configuration Files. Right click on the AN-X2-SQD-MAS ControlLogix Configuration
File link and select Save target to save the current ControlLogix scheduled data
configuration to a file.
Configuring the AN-X Module in RSLogix 5000
To configure the AN-X in RSLogix 5000:
1. Right click on the ControlLogix Ethernet module that will be communicating to the
AN-X and select Add Module. Add a 1756-ENBT/A module.
2. Set the Major Rev to 1.