MVI69E-LDM ♦ "C" Programmable

Contents

Linux Application Development Module

Developer's Manual

ProSoft Technology, Inc.

Page 51 of 130

August 21, 2014

4.2.4 Backplane Sample

The Backplane Sample program shows block transfer communication with the
CompactLogix controller in slot 0 of the CompactLogix rack. The CompactLogix controller
must be loaded with the sample ladder logic and be configured to communicate with the
MVI69E-LDM module. The ladder is

MVI69_LDMACD

.

To run the Backplane sample:

1 Establish a command window using Telnet or similar terminal software on the PC

through either the Ethernet or Serial P1 port.

2 Login

user:

root

password:

password

To execute the sample:

1 Navigate to the default home directory

/psft/sample

and type the command

./Backplane_Sample&

to run this program as a background task.

2 Reviewing the source code for the Backplane Sample, the program:
 registers Linux event handlers using the

signal

function.

 opens a connection to the hardware via the backplane library API using the

open_backplane

routine. The

open_backplane

will:

o

change the module information with the

MVI69_SetModuleInfo

routine.

o

call

MVI69_Open

to get access to the LDM hardware and backplane.

o

read the size of the configured IO using

MVI69_GetIOConfig

.

o

read and display the module identity using

MVI69_GetModuleInfo

.

 sets each of the front panel LEDs to a default using the

MVI69_SetLED

function.

 enters a main (infinite loop) within this loop. The program will:

o

first read the current run/program mode of the processor using

MVI69_GetScanMode

,

and prints the state if it has changed since the last time it was read.

o

wait for an Input Scan from the CompactLogix processor using the

MVI69_WaitForInputScan

function.

Note:

MVI69_WaitForOutputScan

could also be used.

o

MVI69_GetScanCounter

function is used to read the number of the scan. The scan

count modulo 5000 is used in data write (i.e., controller input data) a few lines below.

o

read output data (read data for the module) from the controller using the function

MVI69_ReadOutputImage

.

o

If the second element has changed since the last read, the new data is copied from
the read (controller output) data to the write (controller input) data. If the data has not
changed, the data in the writer buffer is decremented. The scan count (read above)
is written to the 0th element.

o

write the data back for the controller to read using the

MVI69_WriteInputImage

function.