Electro industries/gaugetech – Electro-Voice 1252 User Manual

Page 62

background image

+ + G

A(+) B(-) S - V +

A(+) B(-) S - V +

+ V -

S B(-) A(+)

+ V -

S B(-) A(+)

+ V -

S B(-) A(+)

+ V -

S B(-) A(+)

8

7 6

5

4

3 2

1 C

-

+

Port 1

RS-232 or

RS-485 (Set)

RS-232

RS-485

Port 2

Normally Slave

Modem/Ethernet Gateway

High Speed Inputs

IRIG-B

RS-485 Master

Unicom or Modem Manager

Nexus P40N External Display

Nexus I/O Module

RS-232 Extension

Cable

(1 to 1 wiring)

I/O Modules and Display
require power connections
to the +/- voltage terminals
(dashed lines).

For all communications: S=Shield. This connection is
used to reference the Nexus port to the same
potential as the source. It is not an earth-ground
connection. You must also connect the shield to
earth-ground at one point.

RT=

~120 Ohms

RT=

~120 Ohms

RT=

~120 Ohms

RT=

~120 Ohms

RT=

~120 Ohms

RT=

~120 Ohms

e

Electro Industries/GaugeTech

Doc # E107706 V1.25

5-4

Port 3

Port 4

Figure 5.4: Communication Wiring

NOTE: You may use ANY port to connect a Nexus Display or RS-485 Master. However, if you are using
the Internal Modem (or Network) Option, Port 2 is labeled Modem (Ethernet) Gateway. Ports 1, 3 and 4 DO
NOT change. The I/O Modules MUST use Port 4 (Port 3 is an alternate).
Nexus P40N, P41N or P43N Display is shipped programmed to use Port 3—see section 5.7 for

details.