9.9.1: Overview

Q

The Digital Status Input Module is used for either additional status detect or for accumulating pulses
from external equipment, such as power meters, water meters, etc.

Q

Nexus 1250/1252 Unit supplies power for up to 4 connected Digital Status Input modules. See
section 9.2 for power and communication details. Refer to sections 5.12 - 5.13 to determine if you
must use an additonal power source, such as the EIG PSIO.

9.9.2: Communication

Q

Maximum registers per request, read or write, is 4 registers.orm

Q

The device will operate with the following Default Mode Parameters. See section 9.4.1 for details.

Address

247 (F7H)

Baud Rate

57600 Baud

Transmit Delay Time

20 csec

9.9: Digital Status Input Module

Digital Status Input Module Specifications

Model Number

Communication

Power Requirement

Operating Temperature

Voltage Rating

Detection

Factory Settings

Default Settings

(Reset Button)

8DI1

RS-485, Modbus RTU

Programmable Baud Rates: 4800, 9600, 19200, 57600

15–20Vdc at 50–200 mA;

Nexus 1250/1252 Unit

supports up to 4 Modules

(-20 to 79)°C / (-4 to +158)°F

Up to 300Vdc

Wet/Dry, Auto Detect

Modbus Address: 164

Baud Rate: 57600

Transmit Delay Time: 0

Modbus Address: 247

Baud Rate: 57600

256 byte I2C EEPROM for storage of Programmable

Settings and Nonvolatile Memory

Memory

Transmit Delay Time: 20 csec