Amprobe ACD-16-PRO Clamp-Meters User Manual
Page 15

14
Audible Continuity Tester
Audible threshold: between 10
Ω and 300Ω.
Response time: 250
µs
Frequency
Range Accuracy
5.00Hz ~ 500.0Hz
0.5%+4d
Sensitivity (Sine RMS)
40A range: > 4A
400A range: > 40A
1000A range: > 400A
6
00V range: > 30V
Temperature
RANGE Accuracy
1)
-50
o
C ~ 300
o
C 2.0%
+
3
o
C
-58
o
F ~ 572
o
F 2.0%
+
6
o
F
1)
Add 3
o
C (or 6
o
F) to specified accuracy @ -20
o
C ~ -50
o
C (or @ -4
o
F ~ -58
o
F)
T
ype-K thermocouple range & accuracy not included
ACA Current (Clamp-on)
RANGE Accuracy
1) 2) 3)
50Hz / 60Hz
40.00A, 400.0A, 1000A
1.0% + 5d
45Hz ~500Hz
40.00A, 400.0A
2.0% + 5d
1000A
2.5% + 5d
500Hz ~ 3.1kHz (ACD-16TRMS Pro & ACD-40PQ only)
40.00A, 400.0A
2.0% + 5d
1000A
2.5% + 5d
True RMS models Crest Factor:
< 2.5 : 1 at full scale & < 5.0 : 1 at half scale for 40.00A & 400.0A ranges
< 1.4 : 1 at full scale & < 2.8 : 1 at half scale for 1000A range
1)
Add 8d to specified accuracy while reading is below 10% of range
2)
Induced error from adjacent current-carrying conductor: < 0.06A/A
3)
Specified accuracy is for measurements made at the jaw center. When the conductor is not
positioned at the jaw center, position errors introduced are:
Add 1% to specified accuracy for measurements made WITHIN jaw marking lines (away
from jaw opening)
Add 4% to specified accuracy for measurements made BEYOND jaw marking lines (toward
jaws opening)