Table 12: dhg 20 ton supply air blower performance – Energy Tech Laboratories DHG240 User Manual

Page 17

background image

035-17233-000-C-0702

Unitary Products

17

TABLE 12: DHG 20 TON SUPPLY AIR BLOWER PERFORMANCE

DHG240 - BOTTOM DUCT CONNECTIONS

1, 2

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY

(TURNS

OPEN)

3

CFM

6000

7000

8000

9000

9400

ESP

4

BHP

KW

ESP

4

BHP

KW

ESP

4

BHP

KW

ESP

4

BHP

KW

ESP

4

BHP

KW

208 VOLT AND STANDARD DRIVE

870

6.0

5

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

-

-

-

-

-

-

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

-

-

-

-

-

-

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

-

-

-

950

3.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

980

2.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

1.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

1.0

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.7

7.8

6.6

-

-

-

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

4.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

-

-

-

1050

2.5

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

-

-

-

1065

2.0

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

-

-

-

1100

1.0

2.9

5.6

4.7

2.3

6.8

5.7

1.8

7.9

6.6

-

-

-

-

-

-

230/460 VOLT AND STANDARD DRIVE

870

6.0

5

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

-

-

-

-

-

-

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

-

-

-

-

-

-

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

-

-

-

950

3.5

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

965

2.5

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

2.0

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

1.5

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

-

-

-

1025

1.0

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

-

-

-

230/460 VOLT AND HIGH SPEED DRIVE ACCESSORY

950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

4.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

4.0

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

-

-

-

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

-

-

-

1050

3.0

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

-

-

-

1065

2.5

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

-

-

-

1100

1.5

2.9

5.6

4.7

2.3

6.8

5.7

1.8

7.9

6.6

-

-

-

-

-

-

1120

1.0

3.1

5.8

4.9

2.5

7.0

5.9

1.9

8.3

6.9

-

-

-

-

-

-

1

Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filters and a dry evaporator coil.

2

Refer to the Static Resistance table.

3

DO NOT

close the pulley below one turn open.

4

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.

5

The Factory Setting

This manual is related to the following products: