beautypg.com

Model ei168 rf base, Installation & placement, Technical specification – Ei Electronics RadioLINK Base Smoke & Heat Alarms Ei168 User Manual

Page 2

background image

Model

Ei168 RF Base

Installation & Placement

Place the Ei168 Base on the ceiling/wall and mark the screw holes. Drill with a
suitable drill bit, insert the screw plugs, connect to the nearest mains circuit
and screw the base into position.

The RF Bases should be house coded to prevent possible interference from
neighbouring installations – see instructions for more details.

Alarms should be placed in accordance with the general guidelines shown in
the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of smoke reaching the smoke detector

House Code Procedure

1. Connect the base to the

mains circuit and slide on
associated alarm.

2. Hold the house code switch

(with a small screwdriver)
until the yellow light turns on
and then release

3. Similarly, place other bases

into house code mode

4. Check that the number of

yellow flashes (on each base)
corresponds to the number of
bases in your system

5. Remove all bases from house

code

6. Button test each alarm

(attached to each base) to
check your system

Technical Specification

Sensor

None

Supply Voltage:

230V AC

Battery back-up:

Rechargeable lithium cells

RF Range:

150 meters (min) free space

Range Improvement: Adjustable antenna

RF Visual Indicator:

Amber light flashes continuously
for 1.5 to 3.5 seconds while
transmitting RF signal

RF Frequency:

868.499MHZ (1% duty cycle)

RF Power:

+5dBM

Dimensions:

150mm diameter x 19mm depth

Weight:

168g

Power-On Indicator:

Green light on the attached mains
powered alarm can be seen

Alarm characteristics: Available in the attached alarm

Temperature Range:

0

0

to 40

0

C

Humidity Range:

15% to 95% Relative Humidity

Interconnect:

Up to 12 RadioLINK products

Plastic material:

UL94VO flame retardant

Warranty:

5 year (limited) warranty

Approvals:

RF performance to EN300220-3
EMC performance to EMC 301489-3

Specifications are subject to change

Shannon Free Zone, Shannon, Co. Clare, Ireland.

Ph.

+353 61 471277

Fx.

+353 61 471053

Email.

[email protected]

www.