Model ei168 rf base, Installation & placement, Technical specification – Ei Electronics RadioLINK Base Smoke & Heat Alarms Ei168 User Manual
Page 2
Model
Ei168 RF Base
Installation & Placement
Place the Ei168 Base on the ceiling/wall and mark the screw holes. Drill with a
suitable drill bit, insert the screw plugs, connect to the nearest mains circuit
and screw the base into position.
The RF Bases should be house coded to prevent possible interference from
neighbouring installations – see instructions for more details.
Alarms should be placed in accordance with the general guidelines shown in
the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of smoke reaching the smoke detector
House Code Procedure
1. Connect the base to the
mains circuit and slide on
associated alarm.
2. Hold the house code switch
(with a small screwdriver)
until the yellow light turns on
and then release
3. Similarly, place other bases
into house code mode
4. Check that the number of
yellow flashes (on each base)
corresponds to the number of
bases in your system
5. Remove all bases from house
code
6. Button test each alarm
(attached to each base) to
check your system
Technical Specification
Sensor
None
Supply Voltage:
230V AC
Battery back-up:
Rechargeable lithium cells
RF Range:
150 meters (min) free space
Range Improvement: Adjustable antenna
RF Visual Indicator:
Amber light flashes continuously
for 1.5 to 3.5 seconds while
transmitting RF signal
RF Frequency:
868.499MHZ (1% duty cycle)
RF Power:
+5dBM
Dimensions:
150mm diameter x 19mm depth
Weight:
168g
Power-On Indicator:
Green light on the attached mains
powered alarm can be seen
Alarm characteristics: Available in the attached alarm
Temperature Range:
0
0
to 40
0
C
Humidity Range:
15% to 95% Relative Humidity
Interconnect:
Up to 12 RadioLINK products
Plastic material:
UL94VO flame retardant
Warranty:
5 year (limited) warranty
Approvals:
RF performance to EN300220-3
EMC performance to EMC 301489-3
Specifications are subject to change
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.
+353 61 471277
Fx.
+353 61 471053
Email.
www.
eielectronics.com