Ei Electronics Carbon Mo-noxide Alarm Ei261DENRC User Manual
Model ei261denrc co alarm, Product description, Operation
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.
+353 61 471277
Fx.
+353 61 471053
Email.
Web:
www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice
.
Ei261DENRC DataSht RevA
Model
Ei261DENRC CO Alarm
Remote System Control capability
Easi-fit base
Proven electrochemical sensor
Tamper-proof rechargeable Lithium battery back-up
Unique easy to replace sensor module
Memory feature records if CO has been detected
Easy to use Test/Hush button
Automatic self diagnostics
Digital CO level display
Loud distinctive alarm (85 dB(A) at 3 metres)
Power, alarm and fault indicator lights
Interconnectable to other Ei mains powered alarms
Fast CO test mode
Kitemarked to BSEN 50291:2001
5 Year guarantee (limited)
Product Description
The Ei261DENRC is a Carbon Monoxide(CO) alarm powered by 230V
AC mains power, and has built in tamper proof rechargeable Lithium
cells that act as a battery back up in the event of mains failure. These
rechargeable Lithium cells are designed to have a ten-year life and
outlast the life of the CO alarm. They will provide up to 4 weeks of CO
alarm operation without mains power.
The Ei261DENRC also has
R
emote
C
ontrol capability - allowing the
alarm to be controlled remotely from a Control Switch (Ei1529RC). This
then allows remote Test, Locate and Hush function to be performed. If
the Ei261DENRC is also
interconnected to other Ei „
RC
‟ mains
powered alarms, then the whole system can be controlled remotely. Up
to twelve alarms can be interconnected. A Manual Call Point
(MCP401RC) is also available.
The Ei261DENRC is supplied with an Easi-Fit base that allows very
quick and simple installation of the alarm, combined with simple
removal and replacement. The Easi-Fit base automatically connects
both mains power and battery as the alarm slides on to the base.
The Ei261DENRC uses a high performance electrochemical sensor to
sense CO presence. The sensor can be replaced after 5 years to
provide a combined 10 year protection against CO gas.
The Ei261DENRC has a digital display to show the CO level sensed.
The Ei261DENRC has built in circuitry to aid suppression of voltage
transients and RF interference.
Operation
The green indicator will illuminate to show mains power is
present
The horn will sound and the digital display will show the
level of CO gas sensed
The horn will beep every 40 seconds and the digital display
will show
SF
in the event of a sensor fault
The horn will beep every 40 seconds and the digital display
will show
CP
(
C
onnect
P
ower) to indicate the battery back
up is depleted and needs recharging
The “Test/Hush” button will either silence false alarms (if
briefly pressed) or perform a unit self test (if pressed and
held). Note that the alarm cannot be silenced when sensing
a CO level of 300ppm or above
Memory Feature - when the test button is pressed the horn
will sound and the digital display will show the level of CO
gas previously sensed
When interconnected to other Ei mains powered alarms, an
alarm on one detector will trigger all other interconnected
alarms (only the triggered alarm will flash a red indicator and
show the CO level on the digital display)
MAINS POWERED 230V~
Remote System Control Capability
& Rechargeable Battery Back-Up