Fluidyne Control Systems 6670 Series Fuel Consumption Monitor User Manual
Series 6670 : fuel consumption monitor, Specifications introduction dimensions, Features
Specifications
Introduction
Dimensions
The fuel consumption monitor is high capacity compact
unit for measuring net fuel consumption of high
capacity engines. The unit handles the return flow and
calculates and displays net engine consumption. It is most
suited for use with large Gensets, Ship Propulsion Engines,
etc.
Features
·
·
·
·
·
·
Accuracy guaranteed over 15-1500 LPH consumption.
Measures net consumption with single flow sensor.
Gravity head not essential for operation.
Built in high capacity filter.
Works on 12V / 24V DC power supply.
Provided with sturdy mounting frame.
RS 485 Serial output - optional for PLC / SCADA interface.
·
Measurement Flow Range 150-1500 LPH
Accuracy ±0.5% of reading
Service Diesel
Operating Temp. 0-70 C
Display 8 2 Dot matrix LCD back light display.
Fuel Totaliser - 999999.9 lit.
Engine Run Time - 999999.99 Hrs/mins.
Filter Element 25 micron paper replacable type.
Power Supply 24V DC
Port Size Inlet - 1” BSPF
Outlet - 1” BSPF
Return - 1” BSPF
Mounting MS fabricated frame for ground mounting
of unit.
Serial Output RS 485 MODBUS RTU optional
0
Fuel Inlet
Line
Storage Tank
Injector
Fuel Pump Return
Oil Filter
Return
Suction Filter
Suction Hose
Engine
Water
Seperator
Installation
1"BSPF
Liquid Return
1"BSPF
Liquid Outlet
1"BSPF
Liquid Inlet
Litres
x
:
:
:
:
:
:
:
:
:
:
24V DC
Battery
Fluidyne Control Systems (P) Ltd.
S. No. 79/2,Plot No.12, Near Agarwal Godown, Shivne,
Pune-411 023. India
Tel.: 020-25290504, 25290870 Fax: 020-25292773
E-mail: [email protected]
Series 6670 : Fuel Consumption Monitor
For High Pressure Fuel Injected High Capacity Engines
Capacity : 500-3500 HP
www.fluidyne.co.in