beautypg.com

Notice – Thermo Pride DryR22 (LX-13) User Manual

Page 3

background image

3

LIQUID LINE FILTER-DRIER

The air conditioning unit’s copper spun filter/dryer is located on the liq-

uid line.

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-

tor coil using field supplied refrigerant grade (ACR) copper tubing that is

internally clean and dry. Units should be installed only with the tubing

sizes for approved system combinations as specified in tabular data

sheet. The charge given is applicable for total tubing lengths up to 15

feet. See Application Data Part Number 247077 for installing tubing of

longer lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken

not to damage the couplings or kink the tubing. Use clean hard

drawn copper tubing where no appreciable amount of bending

around obstruction is necessary. If soft copper must be used, care

must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service

access to the coil, air handling system, or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize

noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 1/2" foam rub-

ber insulation (Armaflex or equivalent). Liquid lines that will be

exposed to direct sunlight, high temperatures, or excessive humid-

ity must also be insulated.

5.

Tape and suspend the refrigerant lines as shown. DO NOT allow

tube metal-to-metal contact. See Figure 2.

6.

Use PVC piping as a conduit for all underground installations as

shown in Figure 3. Buried lines should be kept as short as possible

to minimize the build up of liquid refrigerant in the vapor line during

long periods of shutdown

7.

Pack fiberglass insulation and a sealing material such as perma-

gum around refrigerant lines where they penetrate a wall to reduce

vibration and to retain some flexibility.

8.

For systems with total line length exceeding 50 feet, see APPLI-

CATION DATA and worksheet "General Piping Recommendations

and Refrigerant Line Length" for vapor and liquid line sizing, cali-

bration of liquid line pressure loss or gain, determination of vapor

line velocity, elevation limitations, orifice connections, system

charging, traps, etc.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper

and should be brazed with a phosphorous-copper alloy material such

as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units

have reusable service valves on both the liquid and vapor connections.

Units are shipped from factory with a nitrogen holding charge. Refer to

Tabular Data Sheet for refrigerant charge quantities. Reusable service

valves are provided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precau-

tions to assure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valve

by wrapping a wet rag around it as shown in Figure 4. Also, protect all

painted surfaces, insulation, and plastic base during brazing. After braz-

ing, cool joint with wet rag.

Valve can be opened by removing the plunger cap and fully inserting a

hex wrench into the stem and backing out counter-clockwise until valve

stem just touches the chamfered retaining wall.

Replacements for the liquid line drier must be exactly the same as
marked on the original factory drier. See Source 1 for O.E.M. replace-
ment driers.

Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.

Filter-Drier

Source 1 Part No.

Apply with Models

13 SEER

S1-02922156000

1.5 to 3 Tons

S1-02922157000

3.5 to 5 Tons

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal
vapor lines at least 1" every 20 feet toward the outdoor unit to facili-
tate proper oil return.

NOTICE

NOTICE

FIGURE 2: Installation of Vapor Line

FIGURE 3: Underground Installation

Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature required is high enough to
cause oxidation of the copper unless an inert atmosphere is provided.
The flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only
low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.

This is not a backseating valve. The service access port has a valve
core. Opening or closing valve does not close service access port.
If the valve stem is backed out past the chamfered retaining wall, the
O-ring can be damaged causing leakage or system pressure could
force the valve stem out of the valve body possibly causing personal
injury.

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

Insulated Vapor Line

TO INDOOR COIL

Liquid Line

PVC
Conduit

Insulated
Vapor Line

TO OUTDOOR UNIT

Cap