Bacnet/ip configuration – Riello UPS NetMan 204 User Manual
Page 43

BACNET/IP CONFIGURATION
For BACnet/IP configuration, you have to set the following variables using "Expert mode":
set bacnet_enable
false → to disable the service
set bacnet_address
set bacnet_client
For example, if the IP address of your BACnet client is 10.1.10.1 and you want to enable the
BACnet/IP on your NetMan 204, you have to enter in expert mode and type the following
commands:
Netman mainteinance console
Available commands:
help prints this help
get shows all values
set
delete removes VAR
sendtrap
reboot reboot the NetMan
factoryreset restore factory configuration
erasefram erase the FRAM module
exit closes the connection
netman>
set bacnet_enable true
netman>
set bacnet_client 10.1.10.1
- 43 -