Riello UPS NetMan 204 User Manual
Page 40

REGISTER
(1)
UPS - MEASUREMENTS
UNIT
NUMBER ADDRESS
9ч11
8ч10
12
11
Input mains star voltage V1
V
13
12
Input mains star voltage V2
V
14
13
Input mains star voltage V3
V
15
14
Input current phase L1
0.1*A
16
15
Input current phase L2
0.1*A
17
16
Input current phase L3
0.1*A
18
17
Input frequency
0.1*Hz
19ч21
18ч20
22
21
Bypass mains star voltage V1
V
23
22
Bypass mains star voltage V2
V
24
23
Bypass mains star voltage V3
V
25
24
Bypass frequency
0.1*Hz
26
25
Output star voltage V1
V
27
26
Output star voltage V2
V
28
27
Output star voltage V3
V
29ч31
28ч30
32
31
Output current phase L1
0.1*A
33
32
Output current phase L2
0.1*A
34
33
Output current phase L3
0.1*A
35
34
Output peak current phase L1
0.1*A
36
35
Output peak current phase L2
0.1*A
37
36
Output peak current phase L3
0.1*A
38
37
Load phase L1
%
39
38
Load phase L2
%
40
39
Load phase L3
%
41
40
Output active power phase L1
0.1 kW
42
41
Output active power phase L2
0.1 kW
43
42
Output active power phase L3
0.1 kW
44
43
Output frequency
0.1*Hz
45ч47
44ч46
48
47
Battery voltage
0.1*V
49
48
Positive battery voltage
0.1*V
50
49
Negative battery voltage
0.1*V
51
50
Battery current
0.1*A
52
51
Remaining Battery Capacity
%
53
52
54
53
Remaining back-up time
Minutes
55ч58
54ч57
59
58
Total output energy (32 bit)
Least Significant Register
0.1 kWh
60
59
Most Significant Register
61
60
62
61
Internal UPS temperature
°C
63
62
Sensor 1 temperature
°C
64
63
Sensor 2 temperature
°C
65ч72
64ч71
(1)
The register number
n must be addressed n-1 in the data packet.
Some measures may not be available for all the UPS. In this case, the relative register
remains at 0xFFFF value.
- 40 -