Step 3:

Connect gauge & fan

Insert blue tube into the

supply register closest to

the air handler.

Plug in the power adapter.

Blue light indicates that

the power is connected.

Connect yellow and green

tubes to matching color

ports on fan. DO NOT

connect the Speed Control

Cable yet because it will

disable the knob and it is

important to experience

manual operation first.

Connect Flex Duct to fan inlet. The negative pressure

will improve the seals at the registers.

Step 2:

Connect to ducts (cont’d)

Attach the Flange

to main return or

air handler cabinet.

Ensure filter has been

removed.

Attach Flex Duct to

the collar on the

Flange.

Install Range Plug 74 to start,

as most systems can be tested

on this Range Configuration.


29 47 74

Whenever a Range Plug is changed, make sure the

gauge shows the correct Range Plug in Step 4.

Step 2:

Connect to ducts (cont’d)

Use smaller Range Plug numbers for tighter ducts,

and larger numbers for leakier ducts.

If Codes require you to pressurize, pass the test in

the depressurize direction first then connect the

Flex Duct to fan exhaust in order to pressurize. All

other connections remain the same.

pressurize

Inlet

airflow

Exhaust

Inlet

Exhaust

depressurize

airflow